Home : Products : Hach WIMS : Hach WIMS Client : Documentation : Main Menu : Modeling : Solids Production Analysis : Solids Wastage Report
Q11015 - INFO: Solids Wastage Report

The solids wastage report determines the wastage rate to maintain a desired SRT. 

 

USING:

When the Solids Wastage Report form is opened, yesterday's data is pulled up for your MLSS, Eff TSS, RAS TSS, and WAS Flow.  If you want to use a different day to calculate your New Wastage Rate, simply change the Date. 

1. Uncheck all offline Basins and Clarifiers.
2. Enter your estimated Eff Flow and RAS Flow rate from each Clarifier. 
3. Click Calc Report and  your New Total Wastage Flowrate is calculated. 
4. Click Print to send the report to the printer.

BUTTONS:

Sets the day to pull data from.

Calculates the values for the report based on the current settings.

Sends the Report to the printer.

Closes the form.

 

NOTES:

Control of solids retentrion time (SRT) provides a means of regulating the growth rate of microorganisms.  Control of growth rate, in turn, assists in the maintenance of a uniform effluent quality and provides a degree of control over solids production and oxygen utilization rates.  For these reasons, SRT control is one of the more widely used operational strategies for activated sludge systems.  The solids wastage report determines the wastage rate to maintain a desired SRT. 

New Wastage Flowrate (MGD):

 

Note: 0.12 = 1/8.34

 

Related Articles
No Related Articles Available.

Article Attachments
No Attachments Available.

Related External Links
No Related Links Available.
Help us improve this article...
What did you think of this article?

poor 
1
2
3
4
5
6
7
8
9
10

 excellent
Tell us why you rated the content this way. (optional)
 
Approved Comments...
No user comments available for this article.
Created on 4/25/2008 1:43 PM.
Last Modified on 10/12/2008 6:25 AM.
Last Modified by Scott Dorner.
Article has been viewed 4424 times.
Rated 0 out of 10 based on 0 votes.
Print Article
Email Article