Compliance Engine Regulatory Limit Rounding Rule Facility Setting specifies how WIMS values are rounded when compared to the Regulatory Limits
The Setting has the following options:
No Rounding: The value is not rounded.
Variable: The value is rounded to the decimal place setting for the variable. If the variable decimal place setting for the variable is set to 'Not Fixed' no rounding will occur.
Limit: The value is rounded to the number of decimal places that the limit is entered to in Regulatory Limits. Example: Limit is entered at 8.5, the value will be rounded to 1 decimal. NOTE: Zeros are used, example limit is entered as 8.0 will be rounded to 1 decimal place, entered at 8 will be rounded to zero decimal places.
Note: Rounding is scientific.
Limit |
Value |
No Rounding |
Variable |
Limit |
<85.0 Monthly Average |
Comp Eng Calcs Monthly average of 84.9837 |
Violation (84.9837 is less than 85.0) |
No Violation (85 is not less than 85.0). Var's Decimal Place = 0 |
No Violation (84.9837 to 1 decimal is 85.0 which is not less that 85.0) |
<85.0 Monthly Average |
Comp Eng Calcs Monthly average of 84.9211 |
Violation (84.9211 is less than 85.0) |
No Violation (85 is not less than 85.0). Var's Decimal Place = 0 |
Violation (84.9211 to 1 decimal is 84.9 which is less that 85.0) |
>8.5 Daily value |
Entered value of 8.55 |
Violation (8.55 is greater than 8.5) |
Violation (8.6 is greater than 8.5) Var's Decimal Place = 1 |
Violation (8.6 is greater than 8.5) Limit entered to 1 Decimal Place |
>8.5 Daily value |
Entered value of 8.513 |
Violation (8.513 is greater than 8.5) |
Violation (8.51 is greater than 8.5) Var's Decimal Place = 2 |
No Violation (8.5 is not greater that 8.5), Limit entered to 1 decimal place. |
This setting can be set in Facility Setup on the settings tab using Comp Engine Reg Limit Rounding
TECHNOTE: Table SETTINGS, Setting='COMPENG-REGLIMIT-ROUNDRULE'