Home : Supported Variable Configurations for Interface Q12075
Q12095 - INFO: Supported Variable Configurations for Interface Q12075

Supported variable configurations for the Hach WIMS Direct Server-Side Interface to WaterEye Database.

To link a variable to a WaterEye sensor, select Edit/View Variables in the client and select the Interface tab.

Then click Interface To radio button. The drop down box next to the option is now enabled, click the drop down arrow and choose the WaterEye interface name (name given when configuring the interface).

Now you are ready to link a variale to a WaterEye sensor. The Tag name and a statistic are all that are mandatory.

  •  This is the tag name that will be used to link this variable to a WaterEye sensor. The ? symbol (question mark) will allow you to browse for tag names.
  •  This is a listing of all the statistics supported by this interface. This includes the following statistics for a specified time period:

AVERAGE Take the average of the data poins
TOTAL Take the sum total of all values
MINIMUM Get the minimum value
MAXIMUM Get the maximum value
FIRST Get the first value
LAST Get the last value
DIFF Calculate the difference between the first value and the last value
RANGE Calculates the difference between the minimum and maximum values
INVENTORY This is a count of all the values in the file, when the value decreases from previous value and the decrease is greater than the DEADBAND set in Hach WIMS client for the variable
COUNT Get the number of records
TIMEGT(x) Get the number of records with values greater than (x), i.e. TIMEGT(5) would count all values > 5
TIMELT(x) Get the number of records with values less than (x)
TIMEEQ(x) Get the number of records with values equal to (x)

  This is the value to multiply the result by when using parameter variable types. Commonly used to convert from one unit base to another. For example to convert gallons per minute (GPM) to gallons per day (GPD), set the scale factor to 1440 (1440 minutes per day).

  •  All three fields must have numeric values or the word None (as shown). The Low Range and High Range will crop data from the source. For example to eliminate negative numbers from a particular tag, set the Low Range to 0 (zero) - this will get any values equal to or greater than 0 (zero). The Deadband is used for the statistic Inventory and will elliminate noise levels up to the value specified. For example, if you enter .5 next to Deadband, any value change of .5 or less, will be ignored.

    • Start Time will set the beginning of the time slot for this variable.
    • Stop Time will set the ending time for the time slot.
    • Same Day as Start is only used by daily variables and it means the stop time is on the same day as the start time.
    • Day After Start is also only used by daily variables and it means the stop time is a day after the start time.

 

    • Using the Filter Data feature allows you to collect data for the current variable only when certain conditions are met on another tag/sensor. For example, if you wanted to collect the Filtered Turbidity only when the Flow was greater than 0, you can configure that here.
Related Articles
No Related Articles Available.

Article Attachments
No Attachments Available.

Related External Links
No Related Links Available.
Help us improve this article...
What did you think of this article?

poor 
1
2
3
4
5
6
7
8
9
10

 excellent
Tell us why you rated the content this way. (optional)
 
Approved Comments...
No user comments available for this article.
Created on 3/19/2009 4:38 PM.
Last Modified on 5/13/2009 1:45 PM.
Last Modified by No Author Name Available!.
Article has been viewed 2560 times.
Rated 0 out of 10 based on 0 votes.
Print Article
Email Article